Skip to content
Fault? Available day and night, anywhere in the Netherlands: Faults, 24/7: 043 204 18 26 NLENClosed now, open again tomorrow 08:30
Consumer unit and meter cupboard

Wiring in the consumer unit: which wire, which colour, which cross-section

Wire type, colours and cross-section per breaker, plus the mistake that most often causes a hot terminal. Background, not DIY instructions.

Kevin HermansUpdated 19 August 20267 min read

Short answer

Inside the consumer unit you use flexible wire that can take the heat, usually H07V2-K, with ferrules on every end. The cross-section follows the protection: 2.5 mm² at 16A, 4 mm² at 20A, 6 mm² at 25A. The colours are fixed: brown, black or grey for line, blue for neutral, green-yellow for earth.

Who this article is for This is technical background, not DIY instructions. Working in a consumer unit means working right next to a supply that you cannot isolate. Only do this if you are demonstrably competent under NEN 3140. As a homeowner: read along so you understand what your electrician is doing, but leave the work to him.

Which type of wire

A consumer unit gets warm. Components give off heat, the enclosure is closed and there is often little ventilation. That is why you use wire that can cope with it.

H07V2-K is the standard: flexible copper wire with PVC insulation rated up to about 90 degrees. Flexible because you make a lot of tight bends in a consumer unit, and stiff wire then breaks or presses against components.

H07V-U or VD wire (solid) belongs in the fixed installation, in conduit. Not in the consumer unit, because it is too stiff for the bends you make there.

Ferrules are not optional. Flexible wire without a ferrule in a screw terminal means loose strands, poor contact pressure and, in time, heat build-up. Every conductor gets a ferrule, crimped with a good crimping tool, in the colour that matches the cross-section.

Colours

These are fixed and you do not deviate from them, because the next electrician relies on them.

Colour Function
Brown Line (L1)
Black Line (L2)
Grey Line (L3)
Blue Neutral (N)
Green-yellow Earth (PE)

Never use green-yellow for anything else, not even when it happens to be convenient. In principle blue may only be used as neutral.

In older installations you still come across red, white and black from before the European colour code. When replacing a consumer unit that means: measure, do not assume. I have found red wires used as neutral and blue ones as line.

Colour chart of conductor colours with their function

Cross-section: which wire with which breaker

The cross-section follows the protection, not the other way round. The breaker protects the cable, so the cable must be able to carry the current the breaker lets through.

Breaker Minimum cross-section in the consumer unit
B10 / C10 1.5 mm²
B16 / C16 2.5 mm²
B20 / C20 4 mm²
B25 / C25 6 mm²
B32 / C32 6 to 10 mm²
Main switch 40A 10 mm²
Main switch 63A 16 mm²

These are guide values for short lengths inside a consumer unit under normal conditions. With a long cable run or with many cables bundled together you have to go up a size because of voltage drop and heat dissipation.

The mistake made most often: fitting a heavier breaker on existing wiring to "solve" an overloaded circuit. If 2.5 mm² is installed and you fit a 20A breaker, the protection no longer trips before the cable gets hot. That is exactly how you end up with a smouldering cable in a wall. The right solution is an extra circuit, see separate circuits.

Working neatly is not about looks

A neatly wired consumer unit looks good, but that is not why it has to be done.

  • Bundling and routing makes sure no wire lies against a hot component.
  • Leaving space around the components allows air to circulate.
  • Spare wire length at each connection means you can replace a component later without pulling everything again.
  • Strain relief at the entry makes sure a terminal does not come loose if the cable is pulled.
  • Tightening torques as specified by the manufacturer. Too loose causes heat, too tight damages the conductor. This is where most loose connections come from.

That last point is the most underestimated cause of problems in meter cupboards. A terminal tightened by hand on feel can run hot years later. Use a torque screwdriver.

What you can see in a good consumer unit

Even without technical knowledge you can see a lot:

  • Wires run in neat lines, not criss-cross.
  • Every conductor has a ferrule.
  • The colours are used consistently.
  • There is a readable circuit chart.
  • The earths are on an earth bar, not looped from terminal to terminal.
  • There is space left over.

If it looks like spaghetti, that is not a good sign. Not because it is ugly, but because it almost always goes together with other sloppy work that you cannot see.

From my own work

During fault finding in Beek there was a circuit that kept dropping out intermittently. No short circuit to be found, insulation resistance fine. With the thermal imaging camera one terminal on the main switch turned out to be 40 degrees hotter than the rest. The conductor was loose, probably since the installation eight years earlier. Thirty seconds of tightening solved it. Without the camera I could have spent hours looking.

When to call an electrician

If you suspect that sloppy work was done at some point, or if you have a consumer unit that several people have worked on. A check with testing and a thermal imaging scan is usually done within an hour. That can be done on its own, and it is also part of an electrical inspection of your home.

If it is urgent, go to the fault service and choose a time slot yourself. If the whole consumer unit has to go, read how that works in consumer unit replacement.

Call 043 204 18 26WhatsApp a photo

Frequently asked questions

What is H07V2-K wire?

Flexible copper wire with heat-resistant PVC insulation, rated up to about 90 degrees. The standard for wiring inside a consumer unit.

Are ferrules mandatory?

With flexible wire in screw terminals they are essential for a reliable connection. Without a ferrule you get loose strands and poor contact pressure.

Which cross-section goes with a 16A breaker?

At least 2.5 mm² under normal conditions and short lengths. Heavier with long runs or bundling.

May I fit a heavier breaker if a circuit trips too often?

No. The breaker protects the cable. A heavier breaker on the same cable means the cable can get hot before anything switches off.

Why are the conductor colours so important?

Because the next electrician relies on them. A wrongly coloured conductor is a safety risk for anyone who works on it later.

Can a loose terminal really cause a fire?

Yes. Poor contact pressure causes local heat, and that gets worse over the years. That is why tightening torques are part of the job and not a matter of feel.

Further reading

Questions and comments

Ask your question below. Ask before 17:00 on a working day and you get an answer from Kevin himself the same day. No account needed, and your email address does not appear on the site.

This tells me you are not a computer program. Type the answer as a number, for example 12.

Ask your question

Only to let you know there is an answer. It does not appear on the site and does not go on a mailing list.

Comments are read before they appear on the site. I publish questions, corrections, experiences and criticism. I do not publish advertising, or advice that encourages people to work on a live installation.

Call Quote